NOVUS AUTOMATION 2/4
READ HOLDING REGISTERS – 03H
This command can be used for reading one or several holding registers, according to the table in the chapter apart.
WRITE SINGLE COIL - 05H
This command can be used for activating or deactivating one of the digital outputs, according to the table below.
Address Description
0 State of digital output 1 (0000h=deactivate; FF00h=activate)
1 State of digital output 2 (0000h=deactivate; FF00h=activate)
The specified addresses correspond to the low level physical addresses, where zero (0) corresponds to the address of
PLC 10001.
WRITE SINGLE REGISTER – 06H
This command can be used for writing in a holding register, according to the table in the chapter apart.
WRITE MULTIPLE COILS – 0FH
This command can be used for simultaneous activating or deactivating of the two digital outputs, according to the table
below.
Bit Description
0 State of digital output 1 (0=deactivate; 1=activate)
1 State of digital output 2 (0=deactivate; 1=activate)
TABLE OF HOLDING REGISTERS
The specified addresses correspond to the low level physical addresses, where zero (0) corresponds to the address of
PLC 40001. The columns minimum and maximum contain the range of values valid for each parameter. The column R/W
indicates if the parameter is for writing and reading (R/W) or for reading (R) only.
Address Description SuperView Mnemonic Minimum Maximum R/W
0 Series number (word high) - 0 65535 R
1 Series number (word low) - 0 65535 R
2 Baud-rate - 0 7 R/W
3 Modbus Address - 1 247 R/W
4 Parity - 0 2 R/W
5 Firmware version 0 999 R
6 Diagnostic state timer (in tenths of seconds) - 0 600 R/W
7
State of the digital outputs, where bit 0 represents
output 1, bit 1 represents output 2 (0=off; 1=on), etc.
-
0 3 R/W
8 State of digital output 1 (0=off; 1=on) Out1St 0 1 R/W
9 State of digital output 2 (0=off; 1=on) Out2St 0 1 R/W
10 Reserved - 0 0 R
11 Reserved - 0 0 R
12
Value of timing for digital output 1, in hundredths of
seconds - word high
Out1TH
0 65535 R/W
13
Value of timing for digital output 1, in hundredths of
seconds - word low
Out1TL
0 65535 R/W
14
Value of timing for digital output 2, in hundredths of
seconds - word high
Out2TH
0 65535 R/W
15
Value of timing for digital output 2, in hundredths of
seconds - word low
Out2TL
0 65535 R/W
16-19 Reserved - 0 0 R
20
Time for deactivating digital output 1, in hundredths of
seconds - word high
Out1CurTH
0 65535 R
21
Time for deactivating digital output 1, in hundredths of
seconds - word low
Out1CurTL
0 65535 R
22
Time for deactivating digital output 2, in hundredths of
seconds - word high
Out2CurTH
0 65535 R